Thursday, October 24, 2013

Methods of explosion protection for electrical equipment

METHODS OF EXPLOSION PROTECTION

Method                                                                                               Type of Protection

Designed to prevent any means of ignition arising            Ex e Increased Safety

Ex n or Ex N Non Sparking

Designed to limit the ignition energy of the circuit            Ex I Intrinsic Safety

Designed to prevent the flammable mixture reaching    Ex m Encapsulation

a means of ignition                                                                          Ex p Pressurisation

Ex o Oil Immersion

Ex nR or Ex N Restricted Breathing

Designed to prevent any ignition from spreading              Ex d Flameproof Enclosure

Ex q Powder Filling

 

Friday, October 18, 2013

Minimum terminal capacity for copper protective conductors (PE, PEN)

CROSS-SECTIONAL AREA OF PHASE CONDUCTORS S
MM2
MINIMUM CROSS-SECTIONAL AREA OF THE CORRESPONDING PROTECTIVE CONDUCTOR (PE, PEN) SPA
MM2
S ≤ 16
S
16 < S ≤ 35
16
35 < S ≤ 400
S/2
400 < S ≤ 800
200
800 < S
S/4
a Current in the neutral may be influenced where there are significant harmonics in the load.
Minimum terminal capacity for copper protective conductors (PE, PEN)
Source: IEC 61439-1 2011 Table 5

Friday, October 11, 2013

Guide to migration from IEC 60439 to IEC 61439 (XL3 Confugurable Assemblies IEC 60439 >>> IEC 61439)

This document only deals with  distribution enclosures for advanced users (authorised persons), i.e. parts 1 and 2 of the new standard. Part 3 of standard IEC 61439 discusses DBO (Distribution Boards intended to be operated by Ordinary persons) only up to 250 A. One of the new features of this standard is that the table in appendix D (checking the design) covered laterin this document does not apply in 61439-3.

In addition in its new version, standard 61439-3 takes account of domestic normative references.

 

DOWNLOAD :

 

http://www.export.legrand.com/files/fck/pdf-EN/EXB12074_GUIDE_TABLEAUTIERS_EN.pdf