Monday, March 31, 2014
Friday, March 28, 2014
Current carrying capacity of Cu busbar
Size in mm | Area sqmm | Weight/ km | current carrying capacity in amp ( copper ) at 35 deg.C | |||||||
AC ( no. of bus) | DC ( no. of bus) | |||||||||
I | II | III | II II | I | II | III | II II | |||
12X2 | 24 | 0.209 | 110 | 200 | 115 | 205 | ||||
15X2 | 30 | 0.262 | 140 | 200 | 145 | 245 | ||||
15X3 | 75 | 0.396 | 170 | 300 | 175 | 305 | ||||
20X2 | 40 | 0.351 | 185 | 315 | 190 | 325 | ||||
20X3 | 60 | 0.529 | 220 | 380 | 225 | 390 | ||||
20X5 | 100 | 0.882 | 295 | 500 | 300 | 510 | ||||
25X3 | 75 | 0.663 | 270 | 460 | 275 | 470 | ||||
25X5 | 125 | 1.11 | 350 | 600 | 355 | 610 | ||||
30X3 | 90 | 0.796 | 315 | 540 | 320 | 560 | ||||
30X5 | 150 | 1.33 | 400 | 700 | 410 | 720 | ||||
40X3 | 120 | 1.06 | 420 | 710 | 430 | 740 | ||||
40X5 | 200 | 1.77 | 520 | 900 | 530 | 930 | ||||
40X10 | 400 | 3.55 | 760 | 1350 | 1850 | 2500 | 770 | 1400 | 2000 | |
50X5 | 250 | 2.22 | 630 | 1100 | 1650 | 2100 | 650 | 1150 | 1750 | |
50X10 | 500 | 4.44 | 920 | 1600 | 2250 | 3000 | 960 | 1700 | 2500 | |
60X5 | 300 | 2.66 | 760 | 1250 | 1760 | 2400 | 780 | 1300 | 1900 | 2500 |
60X10 | 600 | 5.33 | 1060 | 1900 | 2600 | 3500 | 1100 | 2000 | 2800 | 3600 |
80X5 | 400 | 3.55 | 970 | 1700 | 2300 | 3000 | 1000 | 1800 | 2500 | 3200 |
80X10 | 800 | 7.11 | 1380 | 2300 | 3100 | 4200 | 1450 | 2600 | 3700 | 4800 |
100X5 | 500 | 4.44 | 1200 | 2050 | 2850 | 3500 | 1250 | 2250 | 3150 | 4050 |
100X10 | 1000 | 8.89 | 1700 | 2800 | 3650 | 5000 | 1800 | 3200 | 4500 | 5800 |
120X10 | 1200 | 10.7 | 2000 | 3100 | 4100 | 5700 | 2150 | 3700 | 5200 | 6700 |
160X10 | 1600 | 14.2 | 2500 | 3900 | 5300 | 7300 | 2800 | 4800 | 6900 | 9000 |
200X10 | 2000 | 17.8 | 3000 | 4750 | 6350 | 8800 | 3400 | 6000 | 8500 | 10000 |